@rpannekoek

Description

@rpannekoek

I think I figured out what byte 175 represents: this seems to be the position for the Electronic Expansion Valve (EEV).
From what I observed, the value varies between 40 and 120 (when using getIntMinus1), where 120 represents valve max open.
Interestingly, an EEV typically only has something like 8 positions and if you look at the schematics for the WH-MDC05J3E5, only one of 4 EEV poles are actually connected, so the WH-MDC05J3E5 can actually only set 2 positions (whereas the higher power models do have all 4 EEV poles connected, so can set all 8 positions).
From what I observed on a WH-MDC05J3E5, it switches positions around a value of 50. When it switches, you can observe significant changes in Discharge_Temp (and the difference between Main_Inlet_Temp and Inside_Pipe_Temp).
It's a rather technical, internal reading which you probably won't use to control the heat pump, but it may be an interesting value to monitor and better understand the internal working (I was initially rather surprised by above mentioned changes which did not relate to compressor frequency).